Our
Designs, parts & Dimensions are as per I. S. I Standards. Latest
Innovations are incorporated. Changes are made with times and also
as per Customer demands. |
|
"VIDHATA"
Single/
Double Cylinder, Four stroke, Vertical, Air/Water cooled, with
MICO Fuel Injection equipment, Manual / Semi Automatic and
Automatic Models. |
|
Specially
designed, self-excited and self-regulated in screen protected
drip-proof enclosure, available in Single Phase (230V/50HZ) and
Three Phase (415V/50HZ) at 1500 RPM, Manufactured as per
IS:4722 under strict quality control, Specially designed
heavy-duty with low temperature rise , special carbon brushes,
better air circulation and greater efficiency with + / - 5%
Voltage regulation. |
|
Armatures
are built of high quality Standard Steel Laminations, Securely insulated
from each other and clamped together under high pressure ensuring low
heating losses. Coils and wire-winding is strictly as per insulation class
'B'. Armature are Dynamically Balanced to precise grade using computerised
balancing machine to ensure low vibration operations. Resin Binding means
full protection of Armature in all respects. |
|
Both
D. C. and A. C. Windings are made of highly conductive super-
synthetics enamelled copper wire manufactured by top leading
Companies in India. Highly varnished and dried field coils and
armature windings is of class E insulation. |
|
All
windings are properly varnished in vaccum impregnation machine,
baked for suitable time and at fixed temperature in special
designed Oven. |
|
After
all fittings Rotor is dynamically balanced in a
computerised dynamic balancing machine |
|
Brush
Gear is made of strong, special design- but with simple construction-
making it possible for shafts to rotate easily at low speeds with
noise-free service. Provision for easy access to replace and adjust the
brushes is provided. Brushes are of standard grades, ensuring sparkless
commutation. |
|
Our
Steel made Frames ensure greater strength & standard type production.
Ventilation is provided by strong fan. In case of excess heat due to low
speeds, Blower Mounting arrangement are provided for necessary Cooling. |
|
Our
all products are thoroughly & vigorously tested on special Heavy
Duty Test Bench and Dynamometer. All continuously rated Motors &
Generators are tested on Full Load for more than Five Hours (HEAT RUN
TEST) for temperature rises and the same are not permitted to exceed
values prescribed as per I.S. 4722. All windings are put to insulation
test with lowest rate of 1.5 to 2 KV. |